› Air-cooled Systems
› Liquid-cooled Systems
› Frequently Asked Questions

Liquid-cooled Systems

Model #ASPDS1CCL025ASPDS1CCL035ASPDS1CCL045
Rated Power (LPG/Natural Gas) kW25/2535/3545/45
Voltage (single phase)120/240V120/240V120/240V
Amps @ 120/240V LPG208.3/104.2291.6/145.8333.3/166.6
Amps @ 120/240V NG208.3/104.22291.6/145.8333.3/166.6
Engine/Alternator RPM3600/36003600/36003600/3600
EngineIn-line 4-cyl.In-line 4-cyl.In-line 4-cyl.
Fuel Consumption @ full load
Liquid Propane Gas cu. ft/hr (gal/hr)175 (4.61)223.3 (6.1)286 (7.86)
Natural Gas cu. ft/hr437560560
Dimensions (L”x W”x H”)71 x 29.5 x 3671 x 29.5 x 3677 x 33.5 x 45
Generator Weight (lbs.)79413931414
Automatic Transfer Switch (NEMA 3R)|-------------- 200 Amp with service disconnect --------------|
Enclosure*SteelSteelSteel


Controls
Start/Stop Control Cyclic cranking:7 sec. on, 7 rest.
Automatic Low Oil Shutdown90 sec. total cycle time
High Temperature ShutdownStandard
Overspeed ShutdownStandard (72 Hz)
Overcrank ProtectionStandard
Automatic Voltage RegulatorStandard
Engine Warm-Up (Before transfer to generator)10 seconds
Engine Cool-down (After transfer back to utility)1 minute
Safety FuseStandard
Starter LockoutStarter cannot re-engage until 5 sec. after engine has stopped.
2.5 Amp Timed Trickle Battery ChargerStandard
Mode Switch:
AUTO: Automatic start on utility failure/ 7 days exerciser
OFF: Stops unit. Power is removed. Control and charger still operate.
MANUAL/TEST: Unit remains running. If utility fails, transfer to load takes place.
PLEASE NOTE: This product requires installation involving permanent
outdoor placement, electrical wiring and fuel source connections.
Natural gas pressure of 5” - 14” of water column (0.18 to 0.5 psi) LP
gas pressure of 11”-14” of water column (0.4 to 0.5) is required.